Two-line aspirated smoke fire detector
The detector is based on the National Standard of the People's Republic of China GB15631-2008 "Special Fire Detector" as the main design basis, and is a smoke monitoring device based on advanced laser optical air monitoring technology and microprocessor control technology.
Key words:
Classification:
Aspirated smoke fire detector
Hotline:
Two-line aspirated smoke fire detector
product description
ASD-ZS8102 and ASD-ZS8104 aspirated smoke fire detectors (hereinafter referred to as detectors) are intelligent very early smoke fire detectors with independent intellectual property rights developed by Jiangsu Zhongshi Electronics Co., Ltd. The detector is based on the National Standard of the People's Republic of China GB15631-2008 Special Type Fire Detectors as the main design basis, and is a smoke monitoring device based on advanced laser optical air monitoring technology and microprocessor control technology.
The detector can be used for early warning of various fires that produce smoke in the early stage of the fire, and can be connected with any type of fire alarm controller at home and abroad to form an automatic fire detection and alarm system.
Technical advantages
High sensitivity, can achieve very early fire warning
The aspirated smoke fire detection system is thousands of times more sensitive than traditional point smoke fire detectors and can identify the very early stages of fires and provide early warning. Compared with traditional point-type smoke fire detectors that can trigger an alarm after a fire occurs, the aspirated smoke fire detection system has a huge time advantage.
Good environmental adaptability
It can be used in situations where traditional fire detectors cannot adapt. Such as places with high-speed airflow, large spaces where point-type smoke and temperature-sensing fire detectors are not suitable, above the stage, places with a building height exceeding 12m or with special requirements, low-temperature places, etc.
Good concealment and more beautiful.
Technical Parameters
|
Product Features |
ASD-ZS8102 |
|
Number of sampling tubes |
2 pipes |
|
Self-learning function |
have |
|
Real-time airflow monitoring |
have |
|
Dynamic fault monitoring |
have |
|
Network connection function |
have |
|
remote display |
Optional |
|
Suction pump speed |
Adjustable |
|
Detector operating voltage |
DC24V±15% |
|
Detector operating current |
Normal operating current 800mA, |
|
Relative humidity |
0~96% no condensation |
|
Usage environment |
-40℃~70℃ |
|
Monitor the shading rate range |
0.01~10%obs/m |
|
Sensitivity range |
≤0.8%obs/m |
|
Communication Interface |
RS485 standard communication interface |
|
Programming relay |
5 (expandable) |
|
Sampling conduit size |
Inner diameter 21mm, outer diameter 25mm |
|
Sampling hole diameter |
Diameter 2.0mm, end diameter 8.0mm |
|
Sampling type I catheter length |
Type I pipeline is 130 meters long and the total length is 260 meters |
|
Sampling U-tube length |
Each branch pipeline is 110 meters long, and |
|
Number of sampling type I catheter |
Single pipeline ≤ 28, total number of openings ≤ 56 |
|
|
Each branch pipeline ≤14, |
|
Maximum coverage area |
4400m² |
|
Detector |
L320mm×W255mm×H125mm |